SF6 Gas Leakage Monitoring Sensor FS02102
- NDIR principle applied
- High sensitive, high accuracy
- Corrosion-resistant aluminum alloy shell
- Anti-interference
- Dual-channel, high long-term accuracy data with no drift
- Excellent linear output
- Reliable service for sustainable cooperation
SF6 Gas Leakage Monitoring Sensor FS02102 Introduction
SF6 Gas Leakage Monitoring Sensor FS02102 uses a unique NDIR technology without the need for light source and is equipped with an aluminum alloy shell. It adopts digital output, has the characteristics of anti-interference by other gases, no need for gas pump pipeline, small volume, sturdy and corrosion-resistant shell, easy to use and maintain, and adaptability to harsh environments. It is suitable for leak alarms, environmental detection, online monitoring, gas component analysis, and other applications. Using the non-dispersive infrared principle to detect the presence of sulfur hexafluoride gas in the air, when the infrared light passes through, the transmission intensity of sulfur hexafluoride molecules to a specific wavelength will be significantly weakened. The degree of attenuation is related to the gas concentration, and the relationship between the two follows the Lambert-Beer law.
SF6 Gas Leakage Monitoring Sensor FS02102 Features
1.Detection range
Default: 0~1500PPM (Extendable)
2.Rapid response, high accuracy
Response time: T90 ≤120s (Measured at 50% full scale)
High accuracy: ±25ppm ±2%FS (within standard measurement range)
3.Stable data output
Dual-channel, high long-term accuracy data with no drift
4.Long service life:
The lifetime is up to 10 years (in the air)
5.High detection frequency
The data updates once per second by default.
Application
1.Power distribution room inspection, power equipment monitoring
2.Instrumentation, gas detector
3.Industrial workshop, scientific experiment equipment
4.Gas Leak Monitoring Equipment
Specifications
Specification | Parameter |
Detected Gas | SF6 |
Detection Principle | NDIR |
Detection Range | 0~1500ppm (expandable) |
Solutions | 0.1ppm |
Detection Accuracy | ±25ppm±2%FS (within the standard measuring range) |
Operating Voltage | DC 3.3V~6.0V |
Operating Current | Peak value <180mA, Average ≤45mA. |
Warm-up Time | 1min |
Detection Frequency | Data updated once per second (by default). |
Output mode | Modbus, DAC (0.4V~2V) |
Service Life | 10 Year |
Operation Temperature | -20℃~70℃ |
Operation Humidity | 0~95%RH |
Storage Temperature | -30℃~ 80℃ |
Storage Humidity | 0~95%RH |
Pressure range | 75Kpa~120Kpa |