Industrial Infrared Carbon Dioxide Sensor FS4NDIR/CO2
- High Sensitivity, Stability, and Resolution: Provides precise and reliable measurement results.
- Fast Response: High sensitivity design ensures immediate reaction.
Excellent Interference Resistance: Features temperature compensation, ensuring measurement accuracy.
Industrial Infrared Carbon Dioxide Sensor FS4NDIR/CO2 Introduction
The FS4NDIR/CO2 industrial infrared carbon dioxide sensor uses unique light-cell-free NDIR technology and comes with a robust aluminum alloy casing, supporting digital output. It boasts the following key features:
Interference Resistance: Effectively resists interference from other gases, ensuring measurement accuracy.
Pump-Free Design: No need for pump pipelines, simplifying installation and operation.
Compact Design: Space-saving and suitable for various application environments.
Durable and Corrosion-Resistant: The aluminum alloy casing is robust and corrosion-resistant, suitable for harsh environments.
Easy Maintenance: User-friendly and easy to maintain, saving time and costs.
Product Selling Points
1. High Sensitivity, Stability, and Resolution: Provides precise and reliable measurement results.
2. Fast Response: High sensitivity design ensures immediate reaction.
3. Excellent Interference Resistance: Features temperature compensation, ensuring measurement accuracy.
4. Superior Linear Output: Accurate and consistent data output.
5. Dual Channel Design: Long-term high data accuracy with minimal drift.
6. Long Service Life: Up to 10 years, offering high reliability.
Application
1. Substation Inspection and Power Equipment Monitoring: Ensures the safe operation of power facilities.
2. Instrumentation and Gas Detectors: Used for high-precision gas detection.
3. Industrial Workshops and Scientific Experiment Equipment: Provides reliable environmental monitoring.
4. Gas Leak Monitoring Equipment: Used to detect and alarm gas leaks.
The FS4NDIR/CO2 sensor is an ideal choice for carbon dioxide monitoring in industrial environments, widely applicable in various scenarios, providing efficient and reliable gas monitoring solutions.
Specifications
Performance Parameter | |
Detecting Gas | CO2/Carbon Dioxide |
Range | 0~2000 ppm |
0~6000 ppm | |
0~1%Vol | |
0~3%Vol | |
0~5%Vol | |
Resolution | 1ppm |
Precision | ± (50ppm + 5% of reading) |
Detection principle | principle Non-dispersive Infrared Absorption Detection (NDIR) |
Response time | T90 ≤30s |
Operating Voltage | DC 3.6V~5.0V |
Operating current | ≤85mA (@5V supply) |
Warm-up time | 3min |
Detection Frequency | Data update 1 time per second (default) |
Output Mode | Default Output:Modbus |
Reserved:DAC (0.4V~2V) | |
Lifetime | 10 years (in air) |
Operating Temperature | -20°C to 60°C |
Operating Humidity | 0~95%RH (non-condensing) |
Storage Temperature | -30℃~60℃ |
Storage Humidity | 0~95%RH (non-condensing) |
Pressure range | 75Kpa~120Kpa |